IV Curve Testing

RPT-2026-019 - performed 6 Jul 2026 by Waqar Ahmed

Health score

77

Measurements taken

6

1 outside reference

Findings

2

Customer visibility

Internal only

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)689 VWithin 5% of designPass
Short circuit current (string A)9.1 AWithin 8% of nameplatePass
Earth electrode resistance7.7 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)2 MohmAbove 1 MohmPass
Max module temperature70 CBelow 25 C above ambientOutside reference
Performance ratio on test day62%Baseline 81%Pass
Context
Capacity
5.0 kW
Work order
JOB-2026-0120
Technician
Waqar Ahmed
Recommendation

Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.

Score 77 / 100
Findings

Defects recorded during this inspection.

  • Heavy soiling on lower rows

    MinorOpen

    Dust accumulation reducing output on the two lowest rows more than the rest of the array.

  • String mismatch on MPPT 2

    MajorOpen

    String currents differ by 18 percent, pointing to partial shading or module degradation.