Operations console
Prototype - no backend
All reports
Electrical Safety Audit
RPT-2026-008 - performed 10 Jun 2026 by Waqar Ahmed
Health score
58
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 609 V | Within 5% of design | Pass |
| Short circuit current (string A) | 10.1 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 6.7 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 15 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 61 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 80% | Baseline 81% | Outside reference |
Context
- Site
- Fatima Sheikh
- Customer
- Fatima Sheikh
- Capacity
- 5.0 kW
- Work order
- JOB-2026-0041
- Technician
- Waqar Ahmed
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 58 / 100Findings
Defects recorded during this inspection.
Bird nesting under array
MinorOpenPigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.