Operations console

All reports

Electrical Safety Audit

RPT-2026-008 - performed 10 Jun 2026 by Waqar Ahmed

Health score

58

Measurements taken

6

1 outside reference

Findings

1

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)609 VWithin 5% of designPass
Short circuit current (string A)10.1 AWithin 8% of nameplatePass
Earth electrode resistance6.7 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)15 MohmAbove 1 MohmPass
Max module temperature61 CBelow 25 C above ambientPass
Performance ratio on test day80%Baseline 81%Outside reference
Context
Capacity
5.0 kW
Work order
JOB-2026-0041
Technician
Waqar Ahmed
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 58 / 100
Findings

Defects recorded during this inspection.

  • Bird nesting under array

    MinorOpen

    Pigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.