JOB-2026-0053 - raised via Website 3 mo ago

CompletedNormal priorityQuarterly Care AMC
Checklist

6 of 6 steps complete

Findings

Defects recorded on site. Unresolved criticals roll up to the operations overview.

  • Bird nesting under array

    Minor

    Pigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.

    Resolved

  • Burnt MC4 connector

    Critical

    DC connector on string C shows arcing damage. Replaced on site and adjacent connectors re-terminated.

    Resolved

  • Inverter derating in afternoon peak

    Major

    Unit throttles above 46 degrees ambient. Cooling fins clogged with dust.

    Open

Parts used

Consumed from van stock on this visit.

No parts consumed

Result

Generation either side of the visit.

+7 kWhper day

35 kWh before, 42 kWh after

Worth about Rs 10,710 a month at this site's tariff.

Assignment

Technician

Asif Mehmood
Details
City
Lahore
Capacity
10.0 kW
Raised
29 May 2026, 10:00 AM
Scheduled
29 May 2026, 7:00 PM
SLA due
31 May 2026, 10:00 AM (3 mo ago)
Completed
29 May 2026, 7:00 PM
Services
System Health Audit
Amount
Rs 12,000