Operations console

All work orders

Combiner Box Repair

JOB-2026-0021 - raised via Phone 6 mo ago

CompletedLow priority
Checklist

6 of 6 steps complete

Findings

Defects recorded on site. Unresolved criticals roll up to the operations overview.

  • Monitoring app not configured

    Info

    Customer has no visibility of live generation. App setup offered.

    Resolved

  • Burnt MC4 connector

    Critical

    DC connector on string C shows arcing damage. Replaced on site and adjacent connectors re-terminated.

    Open

  • Earthing resistance above limit

    Major

    Measured 9.4 ohm against a 5 ohm reference. Earth pit needs re-treatment.

    Open

Parts used

Consumed from van stock on this visit.

PartQtyUnit costLine total
Soft Wash Brush Head2Rs 5,940Rs 11,880
Result

Generation either side of the visit.

+20 kWhper day

81 kWh before, 101 kWh after

Worth about Rs 30,000 a month at this site's tariff.

Assignment

Technician

Naveed Iqbal
Details
City
Multan
Capacity
25.0 kW
Raised
27 Feb 2026, 12:00 PM
Scheduled
1 Mar 2026, 6:00 AM
SLA due
2 Mar 2026, 12:00 PM (6 mo ago)
Completed
1 Mar 2026, 6:00 AM
Services
Combiner Box Repair
Amount
Rs 7,800