Operations console

All reports

Thermal Camera Inspection

RPT-2026-026 - performed 1 May 2026 by Danish Ali

Health score

80

Measurements taken

6

1 outside reference

Findings

2

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)726 VWithin 5% of designPass
Short circuit current (string A)8.6 AWithin 8% of nameplatePass
Earth electrode resistance7.9 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)79 MohmAbove 1 MohmOutside reference
Max module temperature53 CBelow 25 C above ambientPass
Performance ratio on test day78%Baseline 85%Pass
Context
Capacity
32.0 kW
Work order
JOB-2026-0090
Technician
Danish Ali
Recommendation

Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.

Score 80 / 100
Findings

Defects recorded during this inspection.

  • Loose structure bolt

    MinorResolved

    Two mid-clamps below torque specification on the north row. Retorqued.

  • Warranty documents missing

    InfoResolved

    Module warranty pack not on file. Copies requested from the original installer.