System Health Audit
RPT-2026-025 - performed 3 Jun 2026 by Naveed Iqbal
Health score
91
Measurements taken
6
0 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 612 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.9 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 9.3 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 53 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 68 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 77% | Baseline 82% | Pass |
Context
- Customer
- Sunrise Poultry Farm
- Capacity
- 25.0 kW
- Work order
- JOB-2026-0093
- Technician
- Naveed Iqbal
Recommendation
System is healthy. Continue the current cleaning cycle and re-inspect in six months.
Score 91 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.