Electrical Safety Audit
RPT-2026-024 - performed 18 Jun 2026 by Waqar Ahmed
Health score
64
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 701 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.1 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 6.4 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 19 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 75 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 69% | Baseline 86% | Outside reference |
Context
- Customer
- Pak Agro Farms
- Capacity
- 25.0 kW
- Work order
- JOB-2026-0099
- Technician
- Waqar Ahmed
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 64 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.