Operations console

All reports

Electrical Safety Audit

RPT-2026-024 - performed 18 Jun 2026 by Waqar Ahmed

Health score

64

Measurements taken

6

1 outside reference

Findings

1

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)701 VWithin 5% of designPass
Short circuit current (string A)9.1 AWithin 8% of nameplatePass
Earth electrode resistance6.4 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)19 MohmAbove 1 MohmPass
Max module temperature75 CBelow 25 C above ambientPass
Performance ratio on test day69%Baseline 86%Outside reference
Context
Capacity
25.0 kW
Work order
JOB-2026-0099
Technician
Waqar Ahmed
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 64 / 100
Findings

Defects recorded during this inspection.

  • No defects found

    InfoResolved

    System operating within expected parameters on the day of inspection.