Operations console
Prototype - no backend
All reports
Insulation Resistance Testing
RPT-2026-022 - performed 10 Jun 2026 by Asif Mehmood
Health score
92
Measurements taken
6
0 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 747 V | Within 5% of design | Pass |
| Short circuit current (string A) | 8.8 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 6.8 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 87 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 50 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 86% | Baseline 79% | Pass |
Context
- Site
- Kamran Yousaf
- Customer
- Kamran Yousaf
- Capacity
- 10.0 kW
- Work order
- JOB-2026-0124
- Technician
- Asif Mehmood
Recommendation
System is healthy. Continue the current cleaning cycle and re-inspect in six months.
Score 92 / 100Findings
Defects recorded during this inspection.
Monitoring app not configured
InfoResolvedCustomer has no visibility of live generation. App setup offered.