Electrical Safety Audit
RPT-2026-016 - performed 6 Apr 2026 by Faisal Shahzad
Health score
59
Measurements taken
6
2 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 613 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 8.8 ohm | Below 5 ohm | Outside reference |
| Insulation resistance (DC+ to earth) | 74 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 65 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 84% | Baseline 84% | Outside reference |
Context
- Customer
- Indus Packaging Ltd
- Capacity
- 150.0 kW
- Work order
- JOB-2026-0145
- Technician
- Faisal Shahzad
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 59 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.