Operations console

All reports

Insulation Resistance Testing

RPT-2026-014 - performed 8 Jun 2026 by Naveed Iqbal

Health score

91

Measurements taken

6

1 outside reference

Findings

1

Customer visibility

Internal only

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)587 VWithin 5% of designPass
Short circuit current (string A)9.5 AWithin 8% of nameplatePass
Earth electrode resistance3.8 ohmBelow 5 ohmOutside reference
Insulation resistance (DC+ to earth)36 MohmAbove 1 MohmPass
Max module temperature47 CBelow 25 C above ambientPass
Performance ratio on test day73%Baseline 85%Pass
Context
Capacity
50.0 kW
Work order
JOB-2026-0017
Technician
Naveed Iqbal
Recommendation

System is healthy. Continue the current cleaning cycle and re-inspect in six months.

Score 91 / 100
Findings

Defects recorded during this inspection.

  • String mismatch on MPPT 2

    MajorResolved

    String currents differ by 18 percent, pointing to partial shading or module degradation.