Insulation Resistance Testing
RPT-2026-014 - performed 8 Jun 2026 by Naveed Iqbal
Health score
91
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 587 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.5 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 3.8 ohm | Below 5 ohm | Outside reference |
| Insulation resistance (DC+ to earth) | 36 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 47 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 73% | Baseline 85% | Pass |
Context
- Customer
- Shahzad Motors
- Capacity
- 50.0 kW
- Work order
- JOB-2026-0017
- Technician
- Naveed Iqbal
Recommendation
System is healthy. Continue the current cleaning cycle and re-inspect in six months.
Score 91 / 100Findings
Defects recorded during this inspection.
String mismatch on MPPT 2
MajorResolvedString currents differ by 18 percent, pointing to partial shading or module degradation.