Earthing Resistance Testing

RPT-2026-013 - performed 16 May 2026 by Naveed Iqbal

Health score

73

Measurements taken

6

1 outside reference

Findings

1

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)562 VWithin 5% of designPass
Short circuit current (string A)9 AWithin 8% of nameplatePass
Earth electrode resistance5.3 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)75 MohmAbove 1 MohmPass
Max module temperature64 CBelow 25 C above ambientPass
Performance ratio on test day67%Baseline 81%Outside reference
Context
Customer
Imran Baig
Capacity
15.0 kW
Work order
JOB-2026-0042
Technician
Naveed Iqbal
Recommendation

Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.

Score 73 / 100
Findings

Defects recorded during this inspection.

  • No defects found

    InfoResolved

    System operating within expected parameters on the day of inspection.