Earthing Resistance Testing
RPT-2026-013 - performed 16 May 2026 by Naveed Iqbal
Health score
73
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 562 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 5.3 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 75 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 64 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 67% | Baseline 81% | Outside reference |
Context
- Site
- Imran Baig
- Customer
- Imran Baig
- Capacity
- 15.0 kW
- Work order
- JOB-2026-0042
- Technician
- Naveed Iqbal
Recommendation
Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.
Score 73 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.