Operations console

All reports

String Testing

RPT-2026-012 - performed 16 Jun 2026 by Faisal Shahzad

Health score

83

Measurements taken

6

1 outside reference

Findings

3

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)757 VWithin 5% of designPass
Short circuit current (string A)8.6 AWithin 8% of nameplatePass
Earth electrode resistance7 ohmBelow 5 ohmOutside reference
Insulation resistance (DC+ to earth)55 MohmAbove 1 MohmPass
Max module temperature67 CBelow 25 C above ambientPass
Performance ratio on test day78%Baseline 84%Pass
Context
Customer
Hina Qureshi
Capacity
7.5 kW
Work order
JOB-2026-0158
Technician
Faisal Shahzad
Recommendation

Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.

Score 83 / 100
Findings

Defects recorded during this inspection.

  • Inverter derating in afternoon peak

    MajorResolved

    Unit throttles above 46 degrees ambient. Cooling fins clogged with dust.

  • Heavy soiling on lower rows

    MinorResolved

    Dust accumulation reducing output on the two lowest rows more than the rest of the array.

  • Earthing resistance above limit

    MajorOpen

    Measured 9.4 ohm against a 5 ohm reference. Earth pit needs re-treatment.