IV Curve Testing
RPT-2026-011 - performed 22 Mar 2026 by Danish Ali
Health score
58
Measurements taken
6
1 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 756 V | Within 5% of design | Pass |
| Short circuit current (string A) | 10.4 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 8.1 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 45 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 51 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 65% | Baseline 80% | Outside reference |
Context
- Customer
- Gulberg Galleria
- Capacity
- 60.0 kW
- Work order
- JOB-2026-0019
- Technician
- Danish Ali
Recommendation
Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.
Score 58 / 100Findings
Defects recorded during this inspection.
Heavy soiling on lower rows
MinorResolvedDust accumulation reducing output on the two lowest rows more than the rest of the array.