Insulation Resistance Testing
RPT-2026-006 - performed 4 Jul 2026 by Danish Ali
Health score
83
Measurements taken
6
2 outside reference
Findings
1
Customer visibility
Internal only
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 758 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.7 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 8.5 ohm | Below 5 ohm | Outside reference |
| Insulation resistance (DC+ to earth) | 43 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 64 C | Below 25 C above ambient | Outside reference |
| Performance ratio on test day | 72% | Baseline 84% | Pass |
Context
- Customer
- Crescent Plaza
- Capacity
- 32.0 kW
- Work order
- JOB-2026-0169
- Technician
- Danish Ali
Recommendation
Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.
Score 83 / 100Findings
Defects recorded during this inspection.
Inverter derating in afternoon peak
MajorOpenUnit throttles above 46 degrees ambient. Cooling fins clogged with dust.