IV Curve Testing
RPT-2026-003 - performed 30 May 2026 by Faisal Shahzad
Health score
85
Measurements taken
6
0 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 602 V | Within 5% of design | Pass |
| Short circuit current (string A) | 9.5 A | Within 8% of nameplate | Pass |
| Earth electrode resistance | 2.5 ohm | Below 5 ohm | Pass |
| Insulation resistance (DC+ to earth) | 73 Mohm | Above 1 Mohm | Pass |
| Max module temperature | 67 C | Below 25 C above ambient | Pass |
| Performance ratio on test day | 66% | Baseline 81% | Pass |
Context
- Site
- Rabia Nawaz
- Customer
- Rabia Nawaz
- Capacity
- 5.0 kW
- Work order
- JOB-2026-0112
- Technician
- Faisal Shahzad
Recommendation
Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.
Score 85 / 100Findings
Defects recorded during this inspection.
No defects found
InfoResolvedSystem operating within expected parameters on the day of inspection.