RPT-2026-001 - performed 14 Jun 2026 by Waqar Ahmed

Health score

63

Measurements taken

6

2 outside reference

Findings

1

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)676 VWithin 5% of designPass
Short circuit current (string A)11.2 AWithin 8% of nameplatePass
Earth electrode resistance2 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)71 MohmAbove 1 MohmOutside reference
Max module temperature46 CBelow 25 C above ambientPass
Performance ratio on test day79%Baseline 83%Outside reference
Context
Capacity
50.0 kW
Work order
JOB-2026-0109
Technician
Waqar Ahmed
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 63 / 100
Findings

Defects recorded during this inspection.

  • No defects found

    InfoResolved

    System operating within expected parameters on the day of inspection.