System Health Audit
RPT-2026-009 - performed 15 Jun 2026 by Danish Ali
Health score
89
Measurements taken
6
4 outside reference
Findings
1
Customer visibility
Shared
Measurements
Each reading against the reference it is judged by.
| Measurement | Reading | Reference | Result |
|---|---|---|---|
| Open circuit voltage (string A) | 614 V | Within 5% of design | Pass |
| Short circuit current (string A) | 12 A | Within 8% of nameplate | Outside reference |
| Earth electrode resistance | 9.5 ohm | Below 5 ohm | Outside reference |
| Insulation resistance (DC+ to earth) | 35 Mohm | Above 1 Mohm | Outside reference |
| Max module temperature | 51 C | Below 25 C above ambient | Outside reference |
| Performance ratio on test day | 79% | Baseline 80% | Pass |
Context
- Customer
- Gulberg Galleria
- Capacity
- 60.0 kW
- Work order
- JOB-2026-0037
- Technician
- Danish Ali
Recommendation
System is healthy. Continue the current cleaning cycle and re-inspect in six months.
Score 89 / 100Findings
Defects recorded during this inspection.
Inverter derating in afternoon peak
MajorResolvedUnit throttles above 46 degrees ambient. Cooling fins clogged with dust.