RPT-2026-007 - performed 12 Mar 2026 by Naveed Iqbal

Health score

77

Measurements taken

6

1 outside reference

Findings

1

Customer visibility

Internal only

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)589 VWithin 5% of designPass
Short circuit current (string A)12.3 AWithin 8% of nameplatePass
Earth electrode resistance5.6 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)62 MohmAbove 1 MohmPass
Max module temperature69 CBelow 25 C above ambientOutside reference
Performance ratio on test day85%Baseline 81%Pass
Context
Customer
Imran Baig
Capacity
15.0 kW
Work order
JOB-2026-0114
Technician
Naveed Iqbal
Recommendation

Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.

Score 77 / 100
Findings

Defects recorded during this inspection.

  • Inverter derating in afternoon peak

    MajorOpen

    Unit throttles above 46 degrees ambient. Cooling fins clogged with dust.