RPT-2026-004 - performed 9 Jun 2026 by Shoaib Akhtar

Health score

65

Measurements taken

6

2 outside reference

Findings

1

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)678 VWithin 5% of designPass
Short circuit current (string A)9.5 AWithin 8% of nameplatePass
Earth electrode resistance8.2 ohmBelow 5 ohmPass
Insulation resistance (DC+ to earth)14 MohmAbove 1 MohmPass
Max module temperature75 CBelow 25 C above ambientOutside reference
Performance ratio on test day83%Baseline 83%Outside reference
Context
Capacity
250.0 kW
Work order
JOB-2026-0076
Technician
Shoaib Akhtar
Recommendation

Schedule corrective repair within 14 days. Losses at the current rate exceed the cost of the fix.

Score 65 / 100
Findings

Defects recorded during this inspection.

  • String mismatch on MPPT 2

    MajorResolved

    String currents differ by 18 percent, pointing to partial shading or module degradation.