Operations console

All reports

Thermal Camera Inspection

RPT-2026-002 - performed 31 May 2026 by Faisal Shahzad

Health score

78

Measurements taken

6

1 outside reference

Findings

2

Customer visibility

Shared

Measurements

Each reading against the reference it is judged by.

MeasurementReadingReferenceResult
Open circuit voltage (string A)774 VWithin 5% of designPass
Short circuit current (string A)11.6 AWithin 8% of nameplatePass
Earth electrode resistance7.9 ohmBelow 5 ohmOutside reference
Insulation resistance (DC+ to earth)45 MohmAbove 1 MohmPass
Max module temperature46 CBelow 25 C above ambientPass
Performance ratio on test day81%Baseline 84%Pass
Context
Capacity
150.0 kW
Work order
JOB-2026-0165
Technician
Faisal Shahzad
Recommendation

Bring cleaning forward by one cycle and re-torque the affected strings within 30 days.

Score 78 / 100
Findings

Defects recorded during this inspection.

  • Hotspot detected on string B

    CriticalOpen

    Thermal scan shows a cell running 27 degrees above array average. Bypass diode failure suspected.

  • Bird nesting under array

    MinorOpen

    Pigeons nesting between modules and roof. Bird mesh recommended for the full perimeter.